Skip to main contentSkip to navigation
Guide

Solar DC cable sizing and design for Perth homes: what installers check

How installers size the DC cable between your panels and inverter in Perth, what AS/NZS 5033:2021 requires, and what to look for on a quote.

By BillWise TeamFiled 19 June 2026Updated 21 Oct 20266 min read

Solar DC cable is sized to limit power lost as heat and to keep the roof cavity safe from fire. In Perth the cable's rating has to be reduced for roof cavity and conduit heat under AS/NZS 5033:2021, and a decent quote lists the cable size.

The direct current (DC) cable runs from your panels to your inverter, the box that turns panel power into household power. It lives in conduit, snakes through the roof cavity and is a pain to replace later. Getting it right the first time is the cheap option.

Why does an installer size DC cable so carefully?

An undersized cable has more resistance, and that resistance turns some of your solar generation into heat instead of electricity. A cable running near its current limit also gets hot, and in a roof cavity that heat is a fire hazard.

The sizing comes down to four inputs:

  • the maximum current the string will carry (panel short-circuit current × the number of parallel strings)
  • the length of the run, since a longer run means more resistance, more heat and a bigger cable
  • the ambient temperature, because a cable's rating drops, or derates, as it gets hotter
  • the installation method: conduit in open air, or enclosed in a roof cavity, which is hotter

How does Perth's heat change the sums?

A lot. AS/NZS 5033:2021 requires cable current ratings to be derated for the installation environment, and a Perth summer is hard on cable.

A typical roof cavity reaches 50–70°C on a hot day. Cable is often rated at 40°C, a common laboratory baseline, so a 6mm² DC cable rated for 40A in open air may be derated to 28–32A in a sealed cavity. Conduit sitting in direct sun on a north-facing roof can hit 80°C+ at the surface, and the cable inside is derated even more. That's why good installers tuck conduit under the roofline or into shade where they can.

Your installer should use the standard's derating tables for your actual roof, not laboratory ratings alone. It's also one reason a slightly larger cable (6mm² rather than 4mm²) often gets specified on longer Perth runs, even when the base current calculation would allow the smaller one.

What cable sizes are common in Perth homes?

Cable size generally climbs with string current and run length. This table is indicative only: the right size depends on your panels, string layout, run length and roof.

Up to 10A (small system)
Typical cable size (short run, < 10m)
4mm²
Typical cable size (long run, > 25m)
6mm²
10–15A (typical 6.6–10kW)
Typical cable size (short run, < 10m)
6mm²
Typical cable size (long run, > 25m)
6mm² or 10mm²
15–20A (larger system with parallel strings)
Typical cable size (short run, < 10m)
6mm²
Typical cable size (long run, > 25m)
10mm²
String current (typical)Typical cable size (short run, < 10m)Typical cable size (long run, > 25m)
Up to 10A (small system)4mm²6mm²
10–15A (typical 6.6–10kW)6mm²6mm² or 10mm²
15–20A (larger system with parallel strings)6mm²10mm²

What should the cable and conduit be?

AS/NZS 5033:2021 says DC cable for solar photovoltaic (PV) systems must be rated for that job. Look for cable marked TUV 2PfG1169 or EN50618 H1Z2Z2-K, the European and Australian-accepted standards for solar DC cable. The sheath resists ultraviolet (UV) light, is double insulated and is rated for continuous outdoor use. Ordinary house wiring cable isn't up to it, because UV and heat break it down much faster. The cable specification should end up in your handover paperwork.

The conduit rules come from AS/NZS 5033:2021 and the AS/NZS 3000 wiring rules, and they're about protection:

  • Roof cavity runs must go in conduit or be otherwise protected from damage. That keeps cable away from roofing nails, keeps DC separate from alternating current (AC) wiring as the standards require, and limits fire spread.
  • External runs need UV-rated conduit, or trunking with a UV-resistant rating. Grey polyvinyl chloride (PVC) conduit yellows and turns brittle in Perth sun within 5–7 years, so ask for UV-stabilised or black high-density polyethylene (HDPE).
  • Roof penetrations must be sealed and flashed against water. A well-installed system has a flashing kit at each one, not just a blob of silicone.

Does voltage drop matter on a long run?

It does, as well as the current rating. A 2% voltage drop is the limit commonly used for DC PV cabling, meaning no more than 2% of the string voltage is lost across the cable's resistance.

Here's an example. Take a 400V DC string with 20m of 6mm² cable carrying 10A. Copper at that size has a resistance of about 3.3 mΩ/m. The conductor length is 20m × 2 = 40m, so the total resistance is 0.132Ω. The voltage drop is 10A × 0.132Ω = 1.32V, which is 0.33% of 400V. Plenty of room.

Stretch the run to 80m (uncommon at home) and the drop rises to 5.28V, about 1.3% of 400V. That's still inside the 2% limit, but longer runs or thinner cable eat the margin quickly.

Perth residential DC runs are typically 5–25m. Beyond 25m, your installer should document the voltage drop calculation.

What should you check on a quote and at handover?

On the quote, look for the cable size in mm², the conduit material and routing, and, for runs over 25m, some sign the installer has allowed for voltage drop.

At handover, ask for the as-installed documentation showing cable routing and sizes. A well-documented job includes the cable specification. Then check three things:

  • external conduit is UV-rated (black HDPE or UV-stabilised grey)
  • roof penetrations are properly flashed
  • DC cable doesn't run alongside AC cable without separation, which AS/NZS 3000 requires

What goes wrong with undersized or poorly installed cable?

Power loss is the quiet problem. It's proportional to current squared times resistance, so a 1% voltage drop means 1% of your DC power is lost as heat every hour the system runs.

The louder problem comes later. Cable that lives near its derated limit slowly cooks its own insulation until it turns brittle and cracks, which opens the door to a ground fault or an arc fault. DC arc faults are more dangerous than AC ones, because a DC arc doesn't self-extinguish at the points where current passes through zero. A damaged DC cable that arcs in a roof cavity is a serious fire risk.

Some modern inverters (certain Sungrow SH and Fronius GEN24 models) include a built-in DC arc fault detection device (AFDD). It watches the string current waveform for arc signatures and trips if it spots one.

Perth's roof temperatures mean the right cable here isn't the one you'd pick for Melbourne. An installer accredited by Solar Accreditation Australia (SAA) sizes to AS/NZS 5033 using derating for the actual roof, so if a quote doesn't list cable sizes, ask.

Good cable protects the output you've paid for, but the bigger number is the system size itself. Get that right first: the BillWise savings calculator takes your usage and shows what different system sizes might save, and the cable spec then makes sure as little of it as possible leaks away.

$Found this helpful? Share it!

Money-relevant figures in this article are checked against primary sources. Here’s how we check our facts.

Run your own numbers

Calculate your savings

See how much you could save with solar, batteries, and smart tariff choices

Related guides

Related articles

How solar panel strings and MPPT work: a Perth buyer's guide

Solar7 min read
Read →

AC coupling vs DC coupling for solar batteries in Perth: what the difference means for you

Solar6 min read
Read →

Adding more solar panels to an existing system in Perth

Solar9 min read
Read →

With your OK we use Google Analytics and Google Ads cookies, Vercel visit statistics, masked session recordings to find bugs, Microsoft Clarity recordings and heatmaps of how pages are used, and an anonymous copy of your calculator figures for local averages. None of it runs unless you accept.